Product description
Distance between tube sheets: 1,000 mm
Number of row: 3
Minimum number of passes = 12 × 3 × 1.5 × 10
–4
= 5.4
This value must be rounded up to 6.
This means that the minimum number of passes is 6 passes.
NOTICE
Nuisance tripping of high-pressure switch
The outdoor unit is equipped with a high-pressure switch, which stops the operation of the air-
conditioning unit for protection when the set high-pressure limit is exceeded. Nuisance tripping
of the high-pressure switch may occur in heating mode if the heat exchanger pipe thermistor
(E2) is not properly positioned or if the limit is not properly set.
Position the heat exchanger pipe thermistor (E2) correctly and set the limit prop-
erly in accordance with the instructions given in this document.
!